Sauter Pressure Control DSB 146 F 001

Sauter Pressure Control DSB 146 F 001
Get Best Offer
Sauter Pressure Control DSB 146 F 001. The function of pressure control is to give security inside the work environment. It prevents the potential damages of over the top pressure from the equipment. Along these lines, workers or users of any pressure equipment are secured. Energy proficiency is improved by control and observing as per needs and with no auxiliary energy.
Brand :

Sauter

Category :

Pressure Measurement

Share :

Distributor Sauter Pressure Control DSB 146 F 001

Sauter Pressure Control  DSB 146 F 001

Specification: 
  • Type: DSB146F001
  • Setting Range: 0...10 bar
  • Switching difference: 0.8...3.7 bar
  • Maximum Pressure: 30 bar
  • Maximum Sensor Temperature: 70 °C
  • Admissible vacuum loading: -1 bar
  • Weight: 0,4 kg
  • Material:  Brass, stainless steel, nitrile rubber
Technical Data:
  • Power Supply: Maximum load with gold-plated contacts 400 mA, 24 V, 10 VA, Minimum load with gold-plated contacts 4 mA, 5 V, Maximum load with silver-plated contacts 10(4) A, 250 V~, 50 W, 250 V=, Minimum load with silver-plated contacts 100 mA, 24 V
  • Parameter: Pressure connection G½" male
  • Ambient Conditions: Admissible ambient temperature -20...70 °C
  • Construction: Housing Transparent cover, Housing material Impact-proof thermoplastic, Device plug Standard plug with female cable connector for cable Ø 6...10 mm
  • Standards and directives: Type of protection IP65 (EN 60529), Protection class I (IEC 60730), Test marks TÜV DWFS (SDBFS) ID: 0000006024, PED 2014/68/EU VdTÜV pressure information sheet 100 cat. IV (as SDBFS) EN 12952-11, EN 12963-9, Ship-approved Germanischer Lloyd (GL) Lloyds Register

Operation:

For directing and observing pressure in fluids, gases and vapors, as per VdTÜV pressure data sheet 100. Particularly reasonable for applications in reduced establishments, for pipe mounting or wall mounting. Whenever the pressure falls beneath the lower change-over point (flexible setpoint XS), the contacts switch from 1-3 to 1-2. At the point when the pressure exceeds the lower change-over point by how much the switching difference XSd, the contacts switch from 1-2 to 1-3.The switching distinction can be set from outside utilizing a grub screw: One revolution changes the switching difference by approx. 20% of the complete switching difference range.

Type

Pressure Control  DSB 146 F 001

Fitur

- For managing and checking pressure in fluids, gases and vapours
- Customizable lower switching point 
- Customizable switching contrast
- Sealable
- Pressure sensor made of brass for non-aggressive media (DSB)
- SIL 2 guaranteed according to EN 61508
- Approved for marine applications (GL and LR guaranteed)